550522_IP BC 60-350 2kV_v02.jpg
The arresters can be installed at the transition 0A to 2 according to the lightning protection zones concept. Single-pole lightning and transient (switching-) surge voltage arrester for the protection of low-voltage electrical distribution systems by industrial, commercial and private use.
  • Combined Arresters Type 1+2 (Class I+II)
  • Test standard: IEC 61643-11 / EN 61643-11
  • On the basis of hermetically sealed rare-gas-filled spark gaps
  • Protection level ? 2 kV
  • Remote signalling contact: break contact
  • High insulation resistance
  • No blow-out vents, thus, not requiring any safety clearance to other installations
  • Optional remonte contact (FM) requiring no additional space
  • EAC certification
IEC category Type 1 + 2 / class I+II
Nominal voltage ACUN 230/400 - 240/415 V~
Max. continuous operating voltage AC (50/60 Hz) Uc 350 V~
Insulation resistanceRisol >10 GΩ
Protection level at 100% lightn. imp. sparkover voltage (1.2/50µs)Up ≤ 2 kV
Protection levelUp ≤ 2,0 kV
Lightning impulse current (10/350 µs) totalItotal 60 kA
Lightning impulse current (10/350 µs) L-N/N-PE/L-PENIimp 60 / - / - kA
Short-circuit withstand capability at max. back-up fuseISCCR 50 kAeff
Max. acceptable back-up fuse F2 (spur wiring) 160 A gG
Additional Information
Max. acceptable back-up fuse F1 (serial wiring) 125 A gG
Operating temperature rangeTU -40 - +80 °C
Max. conductor cross section stranded 50/fine stranded 35 mm²
Recommended conductor cross section 25 mm²
Max. connection torque for terminals 4,0 Nm
Enclosure material / colour polycarbonate (halogen-free) UL 94-V0 / yellow
FM contact / contact type break contact
Switching capacity FM 250 V/2 A
Max. locking torque FM terminals 0,25 Nm
Max. conductor cross section FM 1,5 mm²
Degree of protection (IEC EN 60529) IP 20
Mounting on 35 mm DIN rail (EN 60715)
Dimension (DIN 43880) 2 TE