IP BC 60/FM-350 2kV
Article Nr. : 550523
The arresters can be installed at the transition 0A to 2 according to the lightning protection zones concept. Single-pole lightning and transient (switching-) surge voltage arrester for the protection of low-voltage electrical distribution systems by industrial, commercial and private use.
- Combined Arresters Type 1+2 (Class I+II)
- Test standard: IEC 61643-11 / EN 61643-11
- On the basis of hermetically sealed rare-gas-filled spark gaps
- Protection level ? 2 kV
- Remote signalling contact: break contact
- High insulation resistance
- No blow-out vents, thus, not requiring any safety clearance to other installations
- Optional remonte contact (FM) requiring no additional space
- EAC certification
IEC category | Type 1 + 2 / class I+II |
Nominal voltage ACUN | 230/400 - 240/415 V~ |
Max. continuous operating voltage AC (50/60 Hz) Uc | 350 V~ |
Insulation resistanceRisol | >10 GΩ |
Protection level at 100% lightn. imp. sparkover voltage (1.2/50µs)Up | ≤ 2 kV |
Protection levelUp | ≤ 2,0 kV |
Lightning impulse current (10/350 µs) totalItotal | 60 kA |
Lightning impulse current (10/350 µs) L-N/N-PE/L-PENIimp | 60 / - / - kA |
Short-circuit withstand capability at max. back-up fuseISCCR | 50 kAeff |
Max. acceptable back-up fuse F2 (spur wiring) | 160 A gG |
Additional Information
Max. acceptable back-up fuse F1 (serial wiring) | 125 A gG |
Operating temperature rangeTU | -40 - +80 °C |
Max. conductor cross section | stranded 50/fine stranded 35 mm² |
Recommended conductor cross section | 25 mm² |
Max. connection torque for terminals | 4,0 Nm |
Enclosure material / colour | polycarbonate (halogen-free) UL 94-V0 / yellow |
FM contact / contact type | break contact |
Switching capacity FM | 250 V/2 A |
Max. locking torque FM terminals | 0,25 Nm |
Max. conductor cross section FM | 1,5 mm² |
Degree of protection (IEC EN 60529) | IP 20 |
Mounting on | 35 mm DIN rail (EN 60715) |
Dimension (DIN 43880) | 2 TE |